EA-G-363GD7-A08 C
46.78 kW
Defrost: None
Product code: EA-G-450AG10-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 25,496 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 126.3 m² |
| Inner volume | 61.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 245 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,760 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-450AG10-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.59 | ≈ 12.07 | ≈ 12.13 | ≈ 17.83 |
| 8 | not rated | not rated | not rated | not rated | ≈ 21.86 | ≈ 31.71 | ≈ 34.46 | ≈ 38.67 |
| 10 | not rated | not rated | not rated | not rated | 43.59 | 46.98 | 50.74 | 55.57 |
| 12 | not rated | not rated | not rated | not rated | not rated | 60.55 | 65.51 | 71.51 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 12.48 | 11.02 | ≈ 10.98 | ≈ 10.94 |
| 8 | not rated | not rated | not rated | not rated | 19.89 | ≈ 18.95 | ≈ 29.06 | ≈ 33.01 |
| 10 | not rated | not rated | not rated | not rated | ≈ 27.40 | 39.63 | 43.21 | 47.46 |
| 12 | not rated | not rated | not rated | not rated | not rated | 51.31 | 55.81 | 61.03 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 46.977 | 14.76 | 122.6 |
| Low speed (Y) | 39.629 | 12.45 | 90.8 |
| A | 3787 mm |
|---|---|
| B | 740 mm |
| C | 715 mm |
| F | 660 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3787 mm |
|---|---|
| Width | 740 mm |
| Height | 715 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.