EA-G-180GC10-A01 C
18.39 kW
Defrost: None
Product code: EA-G-450BC7-A09 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 29,056 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 95.6 m² |
| Inner volume | 39.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 183 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,330 rpm |
| Power | 2,840 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.9 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-450BC7-A09 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.20 | 7.92 | 7.94 | ≈ 7.94 |
| 8 | not rated | not rated | not rated | not rated | 13.49 | 12.61 | ≈ 12.62 | ≈ 23.78 |
| 10 | not rated | not rated | not rated | not rated | 19.02 | 18.35 | ≈ 32.97 | 37.72 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 39.93 | 44.98 | 50.18 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 18.350 | 5.76 | 17.8 |
| A | 3787 mm |
|---|---|
| B | 590 mm |
| C | 775 mm |
| F | 510 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3787 mm |
|---|---|
| Width | 590 mm |
| Height | 775 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.