EA-G-540AE7-A01 C
26.45 kW
Defrost: None
Product code: EA-G-450BE7-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 27,681 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 143.4 m² |
| Inner volume | 59.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 222 kg |
| Quantity | 4 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,760 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 63.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-450BE7-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 11.89 | 11.36 | 11.38 | ≈ 11.35 |
| 8 | not rated | not rated | not rated | not rated | 19.42 | 18.12 | ≈ 17.91 | ≈ 32.18 |
| 10 | not rated | not rated | not rated | not rated | 27.25 | 26.38 | ≈ 44.76 | ≈ 51.63 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 53.69 | 61.30 | 68.62 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 11.10 | 10.44 | 10.45 | 10.40 |
| 8 | not rated | not rated | not rated | not rated | 17.96 | 16.87 | ≈ 16.45 | ≈ 16.75 |
| 10 | not rated | not rated | not rated | not rated | 25.04 | 24.36 | ≈ 37.02 | ≈ 44.05 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 32.01 | ≈ 52.05 | 58.77 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 26.376 | 8.28 | 16.2 |
| Low speed (Y) | 24.363 | 7.65 | 14.0 |
| A | 3787 mm |
|---|---|
| B | 640 mm |
| C | 775 mm |
| F | 560 mm |
| E1 | 868 mm |
| E2 | 850 mm |
| E | 3435 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3787 mm |
|---|---|
| Width | 640 mm |
| Height | 775 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.