EA-G-563EC10-A01 C
43.86 kW
Defrost: None
Product code: EA-G-463EC10-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 67,110 m³/h |
|---|---|
| Air throw | 47 m |
| External surface | 129.9 m² |
| Inner volume | 54.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 277 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 10,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 74.0 dB(A) |
|---|---|
| Sound power | 97.5 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-463EC10-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.22 | ≈ 9.66 | ≈ 9.72 | ≈ 15.96 |
| 8 | not rated | not rated | not rated | not rated | ≈ 17.03 | ≈ 28.22 | ≈ 31.49 | ≈ 34.00 |
| 10 | not rated | not rated | not rated | not rated | ≈ 41.51 | 43.77 | 46.46 | 50.82 |
| 12 | not rated | not rated | not rated | not rated | not rated | 57.65 | 61.37 | 66.73 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.71 | ≈ 9.09 | ≈ 9.13 | ≈ 9.14 |
| 8 | not rated | not rated | not rated | not rated | ≈ 16.07 | ≈ 24.20 | ≈ 27.83 | ≈ 30.25 |
| 10 | not rated | not rated | not rated | not rated | ≈ 36.04 | 38.67 | 41.32 | 45.26 |
| 12 | not rated | not rated | not rated | not rated | not rated | 51.09 | 54.61 | 59.39 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 43.770 | 13.75 | 90.6 |
| Low speed (Y) | 38.665 | 12.14 | 72.8 |
| A | 3615 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3615 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.