EA-G-363FC4-A19 C
49.93 kW
Defrost: None
Product code: EA-G-463EC4-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 62,105 m³/h |
|---|---|
| Air throw | 44 m |
| External surface | 267.3 m² |
| Inner volume | 56.1 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 298 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 10,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 96.5 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-463EC4-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.45 | 10.57 | ≈ 10.66 | ≈ 10.72 |
| 8 | not rated | not rated | not rated | not rated | 17.29 | ≈ 17.47 | ≈ 33.06 | ≈ 38.70 |
| 10 | not rated | not rated | not rated | not rated | ≈ 24.89 | 49.92 | 56.40 | 64.40 |
| 12 | not rated | not rated | not rated | not rated | not rated | 72.10 | 78.97 | 87.80 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.92 | 10.04 | 10.11 | ≈ 10.15 |
| 8 | not rated | not rated | not rated | not rated | 16.40 | ≈ 16.45 | ≈ 16.56 | ≈ 33.30 |
| 10 | not rated | not rated | not rated | not rated | ≈ 23.66 | 41.10 | ≈ 48.98 | ≈ 56.52 |
| 12 | not rated | not rated | not rated | not rated | not rated | 62.23 | 69.09 | 77.15 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 49.923 | 15.68 | 42.2 |
| Low speed (Y) | 41.103 | 12.91 | 29.8 |
| A | 3615 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3615 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.