EA-G-563EG4-A06 C
76.11 kW
Defrost: None
Product code: EA-G-463EG10-A11 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
How to read the code of this model.
| Air flow | 57,532 m³/h |
|---|---|
| Air throw | 41 m |
| External surface | 259.8 m² |
| Inner volume | 111.4 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 392 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 10,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 73.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-463EG10-A11 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 19.39 | ≈ 18.08 | ≈ 18.16 | ≈ 18.16 |
| 8 | not rated | not rated | not rated | not rated | ≈ 31.99 | ≈ 47.85 | ≈ 55.26 | ≈ 60.04 |
| 10 | not rated | not rated | not rated | not rated | ≈ 70.73 | 76.31 | 81.63 | 89.38 |
| 12 | not rated | not rated | not rated | not rated | not rated | 100.70 | 107.75 | 117.05 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 18.04 | 16.54 | ≈ 16.59 | ≈ 16.55 |
| 8 | not rated | not rated | not rated | not rated | 29.48 | ≈ 27.41 | ≈ 46.41 | ≈ 51.24 |
| 10 | not rated | not rated | not rated | not rated | ≈ 41.29 | 64.05 | 69.51 | 76.64 |
| 12 | not rated | not rated | not rated | not rated | not rated | 85.18 | 91.95 | 100.37 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 76.312 | 23.96 | 68.9 |
| Low speed (Y) | 64.050 | 20.12 | 50.5 |
| A | 3615 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 3235 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3615 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.