Skip to Content

Brine cooler EA-G-463FC7-A19 C

Brine cooler EA-G-463FC7-A19 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-463FC7-A19 C

Cooling capacity i
40.13 kW
Air flow
48,386 m³/h
Fin spacing
7.0 mm
Air throw
33 m
Fans
4 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 48,386 m³/h
Air throw 33 m
External surface 225.3 m²
Inner volume 68.8 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 321 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 67.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 2"
Outlet 2"
Defrost
EA-G-463FC7-A19 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
40.133 kW Sensible capacity 29.643 kW Fluid flow 12.60 m³/h Pressure drop 33.7 kPa
Cooling capacity · Low speed (Y)
22.433 kW Sensible capacity 16.695 kW Fluid flow 7.05 m³/h Pressure drop 11.9 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 10.49 10.56 10.61 ≈ 10.64
8 not rated not rated not rated not rated 17.44 ≈ 17.02 ≈ 17.09 ≈ 32.51
10 not rated not rated not rated not rated ≈ 24.81 40.13 ≈ 45.88 52.04
12 not rated not rated not rated not rated not rated 57.29 62.95 69.76

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 10.03 9.99 10.03 ≈ 10.05
8 not rated not rated not rated not rated 16.59 16.00 ≈ 16.05 ≈ 28.65
10 not rated not rated not rated not rated 23.51 22.43 ≈ 40.70 46.66
12 not rated not rated not rated not rated not rated ≈ 50.50 56.29 62.64

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 40.133 12.60 33.7
Low speed (Y) 22.433 7.05 11.9

Dimensions

Dimension drawing of EA-G-463FC7-A19 C
Dimension drawing
Dimensions as drawn
A 4415 mm
B 900 mm
C 1190 mm
F 860 mm
E1 1018 mm
E2 1000 mm
E 4035 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4415 mm
Width 900 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.