Skip to Content

Brine cooler EA-G-463FG10-A08 C

Brine cooler EA-G-463FG10-A08 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-463FG10-A08 C

Cooling capacity i
91.56 kW
Air flow
57,488 m³/h
Fin spacing
10.0 mm
Air throw
41 m
Fans
4 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 57,488 m³/h
Air throw 41 m
External surface 324.7 m²
Inner volume 136.2 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 457 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,340 rpm
Power 7,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 75.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
EA-G-463FG10-A08 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
91.560 kW Sensible capacity 66.500 kW Fluid flow 28.75 m³/h Pressure drop 115.9 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
78.558 kW Sensible capacity 56.882 kW Fluid flow 24.68 m³/h Pressure drop 88.5 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 23.01 ≈ 21.17 ≈ 21.24 ≈ 34.57
8 not rated not rated not rated not rated ≈ 59.41 ≈ 62.61 ≈ 67.41 ≈ 72.38
10 not rated not rated not rated not rated 87.75 91.56 96.72 104.82
12 not rated not rated not rated not rated not rated 118.21 125.66 135.72

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 21.45 ≈ 19.43 ≈ 19.47 ≈ 28.35
8 not rated not rated not rated not rated ≈ 34.83 ≈ 52.99 ≈ 57.26 ≈ 62.74
10 not rated not rated not rated not rated ≈ 74.28 78.56 83.56 90.82
12 not rated not rated not rated not rated not rated 101.59 108.52 117.46

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 91.560 28.75 115.9
Low speed (Y) 78.558 24.68 88.5

Dimensions

Dimension drawing of EA-G-463FG10-A08 C
Dimension drawing
Dimensions as drawn
A 4415 mm
B 1100 mm
C 1190 mm
F 1060 mm
G 1135 mm
E1 1018 mm
E2 1000 mm
E 4035 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4415 mm
Width 1100 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.