Skip to Content

Brine cooler EA-G-463FG4-A19 C

Brine cooler EA-G-463FG4-A19 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-463FG4-A19 C

Cooling capacity i
88.53 kW
Air flow
41,817 m³/h
Fin spacing
4.6 mm
Air throw
29 m
Fans
4 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 41,817 m³/h
Air throw 29 m
External surface 668.3 m²
Inner volume 139.4 dm³
Fin spacing 4.6 mm
Fin materialAluminium
Net weight 508 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 66.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
EA-G-463FG4-A19 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
88.529 kW Sensible capacity 63.834 kW Fluid flow 27.80 m³/h Pressure drop 37.3 kPa
Cooling capacity · Low speed (Y)
45.303 kW Sensible capacity 32.996 kW Fluid flow 14.23 m³/h Pressure drop 11.3 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 21.77 21.65 ≈ 21.74 ≈ 21.77
8 not rated not rated not rated not rated 36.17 ≈ 34.61 ≈ 60.54 ≈ 72.32
10 not rated not rated not rated not rated ≈ 51.37 88.53 99.74 112.14
12 not rated not rated not rated not rated not rated 122.32 134.50 148.57

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 20.37 19.89 19.96 ≈ 19.88
8 not rated not rated not rated not rated 33.45 31.34 ≈ 31.37 ≈ 59.07
10 not rated not rated not rated not rated 47.13 45.30 ≈ 81.93 92.97
12 not rated not rated not rated not rated not rated ≈ 99.43 111.21 123.16

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 88.529 27.80 37.3
Low speed (Y) 45.303 14.23 11.3

Dimensions

Dimension drawing of EA-G-463FG4-A19 C
Dimension drawing
Dimensions as drawn
A 4415 mm
B 1100 mm
C 1190 mm
F 1060 mm
E1 1018 mm
E2 1000 mm
E 4035 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4415 mm
Width 1100 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.