Product code: EA-G-463GD10-A08 C

Cooling capacity i
66.53 kW
Air flow
67,088 m³/h
Fin spacing
10.0 mm
Air throw
46 m
Fans
4 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 67,088 m³/h
Air throw 46 m
External surface 264.5 m²
Inner volume 112.3 dm³
Fin spacing 10.0 mm
Fin materialAluminium
Net weight 434 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,340 rpm
Power 7,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 74.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-463GD10-A08 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
66.530 kW Sensible capacity 48.928 kW Fluid flow 20.90 m³/h Pressure drop 62.9 kPa
Cooling capacity · Low speed (Y)
57.953 kW Sensible capacity 42.506 kW Fluid flow 18.20 m³/h Pressure drop 49.2 kPa

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 15.98 15.81 ≈ 15.87 ≈ 15.90
8 not rated not rated not rated not rated ≈ 26.38 ≈ 25.30 ≈ 47.99 ≈ 52.77
10 not rated not rated not rated not rated ≈ 60.82 66.53 71.77 79.00
12 not rated not rated not rated not rated not rated 88.15 94.86 103.63

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 15.16 14.79 ≈ 14.83 ≈ 14.83
8 not rated not rated not rated not rated 24.86 ≈ 23.49 ≈ 41.79 ≈ 46.64
10 not rated not rated not rated not rated ≈ 34.97 57.95 63.33 70.10
12 not rated not rated not rated not rated not rated 77.43 83.93 91.97

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 66.530 20.90 62.9
Low speed (Y) 57.953 18.20 49.2

Dimensions

Dimension drawing of EA-G-463GD10-A08 C
Dimension drawing
Dimensions as drawn
A 5615 mm
B 950 mm
C 1190 mm
F 910 mm
G 985 mm
E1 1318 mm
E2 1300 mm
E 5235 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 5615 mm
Width 950 mm
Height 1190 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.