EA-G-663EE4-A06 C
94.42 kW
Defrost: None
Product code: EA-G-480GE10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 81,792 m³/h |
|---|---|
| Air throw | 45 m |
| External surface | 380.9 m² |
| Inner volume | 163.1 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 659 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 7,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 86.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-480GE10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 22.93 | 22.69 | ≈ 22.77 | ≈ 22.77 |
| 8 | not rated | not rated | not rated | not rated | ≈ 37.80 | ≈ 36.19 | ≈ 68.48 | ≈ 75.18 |
| 10 | not rated | not rated | not rated | not rated | ≈ 86.05 | 94.72 | 102.08 | 112.30 |
| 12 | not rated | not rated | not rated | not rated | not rated | 125.44 | 134.95 | 147.10 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 21.26 | 20.64 | ≈ 20.69 | ≈ 20.64 |
| 8 | not rated | not rated | not rated | not rated | 34.70 | ≈ 32.57 | ≈ 56.11 | ≈ 62.98 |
| 10 | not rated | not rated | not rated | not rated | ≈ 48.67 | 77.69 | 85.56 | 94.60 |
| 12 | not rated | not rated | not rated | not rated | not rated | 104.24 | 113.28 | 123.92 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 94.724 | 29.75 | 62.2 |
| Low speed (Y) | 77.686 | 24.40 | 43.7 |
| A | 5615 mm |
|---|---|
| B | 1050 mm |
| C | 1430 mm |
| F | 1010 mm |
| G | 1115 mm |
| E1 | 1318 mm |
| E2 | 1300 mm |
| E | 5235 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5615 mm |
|---|---|
| Width | 1050 mm |
| Height | 1430 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.