EA-G-450AC10-A10 C
14.43 kW
Defrost: None
Product code: EA-G-535BE7-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 11,144 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 73.8 m² |
| Inner volume | 30.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 122 kg |
| Quantity | 5 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 825 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 77.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-G-535BE7-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.64 | 5.82 | 5.82 | ≈ 5.79 |
| 8 | not rated | not rated | not rated | not rated | 10.66 | 10.09 | ≈ 9.85 | ≈ 16.27 |
| 10 | not rated | not rated | not rated | not rated | 14.76 | 14.45 | ≈ 21.98 | 24.76 |
| 12 | not rated | not rated | not rated | not rated | not rated | 26.22 | 29.30 | 32.42 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 14.448 | 4.54 | 23.9 |
| A | 2857 mm |
|---|---|
| B | 573 mm |
| C | 535 mm |
| F | 395 mm |
| E1 | 518 mm |
| E2 | 500 mm |
| E | 2535 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2857 mm |
|---|---|
| Width | 573 mm |
| Height | 535 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.