EA-G-163FD4-A19 C
18.75 kW
Defrost: None
Product code: EA-G-540AG10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 13,780 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 89.1 m² |
| Inner volume | 44.0 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 170 kg |
| Quantity | 5 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 65.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-540AG10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 8.70 | 7.68 | 7.66 | ≈ 7.63 |
| 8 | not rated | not rated | not rated | not rated | 13.86 | 13.21 | ≈ 13.05 | ≈ 21.18 |
| 10 | not rated | not rated | not rated | not rated | 19.11 | 18.82 | ≈ 28.22 | 31.70 |
| 12 | not rated | not rated | not rated | not rated | not rated | 33.43 | 37.31 | 41.28 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 18.819 | 5.91 | 26.2 |
| A | 3117 mm |
|---|---|
| B | 686 mm |
| C | 605 mm |
| F | 495 mm |
| E1 | 568 mm |
| E2 | 550 mm |
| E | 2785 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 3117 mm |
|---|---|
| Width | 686 mm |
| Height | 605 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.