Cooling capacity i
37.98 kW
Air flow
35,334 m³/h
Fin spacing
7.0 mm
Air throw
23 m
Fans
5 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 35,334 m³/h
Air throw 23 m
External surface 101.7 m²
Inner volume 39.3 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 202 kg
Fans
Quantity 5
Diameter 500 mm
Speed 1,360 rpm
Power 3,450 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 64.0 dB(A)
Sound power 87.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-550AC7-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
37.976 kW Sensible capacity 27.872 kW Fluid flow 11.93 m³/h Pressure drop 104.5 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
33.114 kW Sensible capacity 24.240 kW Fluid flow 10.40 m³/h Pressure drop 82.1 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 8.37 ≈ 8.33 ≈ 8.40 ≈ 14.06
8 not rated not rated not rated not rated ≈ 13.91 ≈ 23.62 ≈ 27.84 ≈ 30.63
10 not rated not rated not rated not rated ≈ 34.65 37.98 41.28 45.73
12 not rated not rated not rated not rated not rated 50.17 54.49 59.94

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 7.96 7.82 ≈ 7.87 ≈ 7.90
8 not rated not rated not rated not rated 13.13 ≈ 12.48 ≈ 24.07 ≈ 27.03
10 not rated not rated not rated not rated ≈ 18.57 33.11 36.38 40.44
12 not rated not rated not rated not rated not rated 44.00 48.08 52.97

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 37.976 11.93 104.5
Low speed (Y) 33.114 10.40 82.1

Dimensions

Dimension drawing of EA-G-550AC7-A10 C
Dimension drawing
Dimensions as drawn
A 4387 mm
B 590 mm
C 715 mm
F 510 mm
E1 818 mm
E2 800 mm
E 4035 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4387 mm
Width 590 mm
Height 715 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.