Skip to Content

Brine cooler EA-G-550BC4-A10 C

Brine cooler EA-G-550BC4-A10 C
Illustrative photo

Producer: Karyer · Line: EA-G (General)

Product code: EA-G-550BC4-A10 C

Cooling capacity i
54.46 kW
Air flow
34,799 m³/h
Fin spacing
4.2 mm
Air throw
23 m
Fans
5 × ⌀500 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Model nomenclature

How to read the code of this model.

  • B
    Number of fans: 5 — Digit 1-9.
  • C
    Fan diameter: 50 — Ø500 mm
  • E
    Coil tube rows (2nd dimensional letter): C — 4 tube rows
  • F
    Fin spacing: 4 — 4.2-4.6 mm
  • G
    Generation code: A — generation A
  • H
    Fan data (fan motor code): 10 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 34,799 m³/h
Air throw 23 m
External surface 178.4 m²
Inner volume 48.0 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 225 kg
Fans
Quantity 5
Diameter 500 mm
Speed 1,360 rpm
Power 3,450 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 64.0 dB(A)
Sound power 87.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
EA-G-550BC4-A10 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
54.458 kW Sensible capacity 39.572 kW Fluid flow 17.11 m³/h Pressure drop 134.4 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
46.849 kW Sensible capacity 33.961 kW Fluid flow 14.72 m³/h Pressure drop 103.0 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 11.06 ≈ 10.99 ≈ 11.04 ≈ 20.12
8 not rated not rated not rated not rated ≈ 18.50 ≈ 35.43 ≈ 39.26 ≈ 43.53
10 not rated not rated not rated not rated ≈ 50.84 54.46 58.64 64.41
12 not rated not rated not rated not rated not rated 71.36 76.99 84.12

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 10.50 ≈ 10.27 ≈ 10.31 ≈ 10.30
8 not rated not rated not rated not rated ≈ 17.41 ≈ 29.41 ≈ 33.19 ≈ 37.86
10 not rated not rated not rated not rated ≈ 42.73 46.85 50.87 56.02
12 not rated not rated not rated not rated not rated 61.59 66.79 73.07

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 54.458 17.11 134.4
Low speed (Y) 46.849 14.72 103.0

Dimensions

Dimension drawing of EA-G-550BC4-A10 C
Dimension drawing
Dimensions as drawn
A 4387 mm
B 590 mm
C 775 mm
F 510 mm
E1 818 mm
E2 800 mm
E 4035 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 4387 mm
Width 590 mm
Height 775 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.