EA-G-550BE7-A10 C
52.72 kW
Defrost: None
Product code: EA-G-563ED10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 43,231 m³/h |
|---|---|
| Air throw | 25 m |
| External surface | 202.6 m² |
| Inner volume | 88.5 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 379 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,000 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 81.3 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| EA-G-563ED10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.65 | ≈ 12.48 | ≈ 12.51 | ≈ 19.21 |
| 8 | not rated | not rated | not rated | not rated | ≈ 22.32 | ≈ 35.53 | ≈ 38.79 | ≈ 41.54 |
| 10 | not rated | not rated | not rated | not rated | ≈ 50.08 | 52.47 | 55.65 | 60.42 |
| 12 | not rated | not rated | not rated | not rated | not rated | 67.92 | 72.35 | 78.32 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 52.473 | 16.48 | 99.5 |
| A | 4415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4035 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.