EA-G-480GC10-A01 C
68.07 kW
Defrost: None
Product code: EA-G-563FC7-A08 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 79,651 m³/h |
|---|---|
| Air throw | 46 m |
| External surface | 281.7 m² |
| Inner volume | 88.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 393 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,340 rpm |
| Power | 9,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 75.0 dB(A) |
|---|---|
| Sound power | 99.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-563FC7-A08 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.92 | ≈ 14.04 | ≈ 14.12 | ≈ 27.24 |
| 8 | not rated | not rated | not rated | not rated | ≈ 22.98 | ≈ 43.48 | ≈ 48.55 | 52.29 |
| 10 | not rated | not rated | not rated | not rated | ≈ 64.26 | 67.69 | 71.61 | 78.31 |
| 12 | not rated | not rated | not rated | not rated | not rated | 89.29 | 94.86 | 102.97 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 13.18 | ≈ 13.29 | ≈ 13.36 | ≈ 23.22 |
| 8 | not rated | not rated | not rated | not rated | ≈ 21.89 | ≈ 37.40 | ≈ 43.07 | ≈ 46.77 |
| 10 | not rated | not rated | not rated | not rated | ≈ 56.00 | 60.01 | 63.94 | 70.14 |
| 12 | not rated | not rated | not rated | not rated | not rated | 79.42 | 84.79 | 92.20 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 67.685 | 21.26 | 90.1 |
| Low speed (Y) | 60.010 | 18.85 | 72.8 |
| A | 5415 mm |
|---|---|
| B | 900 mm |
| C | 1190 mm |
| F | 860 mm |
| G | 935 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5415 mm |
|---|---|
| Width | 900 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.