EA-G-480GD7-A01 C
95.75 kW
Defrost: None
Product code: EA-G-563FD4-A19 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 57,015 m³/h |
|---|---|
| Air throw | 33 m |
| External surface | 522.1 m² |
| Inner volume | 108.4 dm³ |
| Fin spacing | 4.6 mm |
| Fin material | Aluminium |
| Net weight | 490 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,250 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| EA-G-563FD4-A19 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | ≈ 18.16 | ≈ 18.32 | ≈ 33.20 | 37.95 |
| 8 | not rated | not rated | not rated | not rated | ≈ 58.83 | ≈ 63.40 | ≈ 69.04 | 75.01 |
| 10 | not rated | not rated | not rated | not rated | 91.45 | 96.00 | 101.77 | 111.19 |
| 12 | not rated | not rated | not rated | not rated | not rated | 125.70 | 134.05 | 145.67 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 17.21 | ≈ 17.26 | ≈ 17.34 | ≈ 32.00 |
| 8 | not rated | not rated | not rated | not rated | ≈ 28.74 | ≈ 54.44 | ≈ 59.97 | ≈ 66.19 |
| 10 | not rated | not rated | not rated | not rated | ≈ 78.73 | 83.78 | 89.51 | 98.02 |
| 12 | not rated | not rated | not rated | not rated | not rated | 109.85 | 117.80 | 128.22 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 95.997 | 30.15 | 116.5 |
| Low speed (Y) | 83.775 | 26.31 | 91.4 |
| A | 5415 mm |
|---|---|
| B | 950 mm |
| C | 1190 mm |
| F | 910 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 5035 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5415 mm |
|---|---|
| Width | 950 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.