EA-G-440AC10-A01 C
8.78 kW
Defrost: None
Product code: EA-G-630BC10-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 7,789 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 25.6 m² |
| Inner volume | 12.9 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 72 kg |
| Quantity | 6 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 372 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 50.0 dB(A) |
|---|---|
| Sound power | 72.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-G-630BC10-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 2.90 | 2.55 | ≈ 2.57 | ≈ 2.57 |
| 8 | not rated | not rated | not rated | not rated | 4.65 | ≈ 4.43 | ≈ 6.42 | ≈ 7.33 |
| 10 | not rated | not rated | not rated | not rated | ≈ 6.43 | 8.79 | 9.73 | 10.82 |
| 12 | not rated | not rated | not rated | not rated | not rated | 11.62 | 12.77 | 14.07 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 8.787 | 2.76 | 71.4 |
| A | 2557 mm |
|---|---|
| B | 517 mm |
| C | 445 mm |
| F | 345 mm |
| E1 | 385 mm |
| E2 | 367 mm |
| E | 2235 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2557 mm |
|---|---|
| Width | 517 mm |
| Height | 445 mm |
Our engineers answer with a selection for your conditions.