EA-G-380GD4-A01 C
82.65 kW
Defrost: None
Product code: EA-G-663EG7-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 43,882 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 540.8 m² |
| Inner volume | 173.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 578 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 83.2 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| EA-G-663EG7-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 22.72 | 22.17 | ≈ 22.23 | ≈ 22.17 |
| 8 | not rated | not rated | not rated | not rated | 37.14 | ≈ 34.93 | ≈ 57.54 | ≈ 67.25 |
| 10 | not rated | not rated | not rated | not rated | ≈ 52.12 | 82.40 | 91.68 | 101.93 |
| 12 | not rated | not rated | not rated | not rated | not rated | 112.02 | 122.22 | 133.92 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 82.397 | 25.88 | 35.3 |
| A | 5215 mm |
|---|---|
| B | 1100 mm |
| C | 1190 mm |
| F | 1060 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 4835 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5215 mm |
|---|---|
| Width | 1100 mm |
| Height | 1190 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.