EA-GA-335BE7-A21 C
11.67 kW
Defrost: None
Product code: EA-GA-150AE7-A21 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 7,214 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 58.9 m² |
| Inner volume | 16.3 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 97 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 680 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 78.8 dB(A) |
| Energy class | E |
| Inlet | Ø3/4" |
|---|---|
| Outlet | Ø3/4" |
| EA-GA-150AE7-A21 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 4.08 | ≈ 3.63 | ≈ 3.64 | ≈ 3.68 |
| 8 | not rated | not rated | not rated | not rated | ≈ 6.54 | ≈ 7.53 | ≈ 8.47 | ≈ 9.25 |
| 10 | not rated | not rated | not rated | not rated | 10.93 | 11.69 | 12.48 | 13.65 |
| 12 | not rated | not rated | not rated | not rated | not rated | 15.32 | 16.39 | 17.81 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 11.689 | 3.67 | 147.0 |
| A | 1487 mm |
|---|---|
| B | 950 mm |
| C | 810 mm |
| F | 710 mm |
| E | 1035 mm |
| D IN | Ø3/4" |
| D OUT | Ø3/4" |
| Length | 1487 mm |
|---|---|
| Width | 950 mm |
| Height | 810 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.