EA-GA-635BE7-A21 C
23.23 kW
Defrost: None
Product code: EA-GA-250AE7-A21 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 14,429 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 117.9 m² |
| Inner volume | 32.8 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 165 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.8 dB(A) |
| Energy class | E |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| EA-GA-250AE7-A21 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.91 | ≈ 6.28 | ≈ 6.30 | ≈ 6.30 |
| 8 | not rated | not rated | not rated | not rated | ≈ 11.24 | ≈ 14.80 | ≈ 16.84 | ≈ 18.35 |
| 10 | not rated | not rated | not rated | not rated | 21.62 | 23.20 | 24.80 | 27.16 |
| 12 | not rated | not rated | not rated | not rated | not rated | 30.47 | 32.63 | 35.49 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 23.201 | 7.29 | 105.9 |
| A | 2487 mm |
|---|---|
| B | 950 mm |
| C | 810 mm |
| F | 710 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 2487 mm |
|---|---|
| Width | 950 mm |
| Height | 810 mm |
Our engineers answer with a selection for your conditions.