Skip to Content

Brine cooler EA-GA-363BE7-A27 C

Brine cooler EA-GA-363BE7-A27 C
Illustrative photo

Producer: Karyer · Line: EA-GA (Fruit and Vegetable)

Product code: EA-GA-363BE7-A27 C

Cooling capacity i
43.43 kW
Air flow
25,302 m³/h
Fin spacing
7.0 mm
Air throw
25 m
Fans
3 × ⌀630 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 25,302 m³/h
Air throw 25 m
External surface 216.1 m²
Inner volume 61.9 dm³
Fin spacing 7.0 mm
Fin materialAluminium
Net weight 290 kg
Fans
Quantity 3
Diameter 630 mm
Speed 890 rpm
Power 1,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 55.0 dB(A)
Sound power 78.0 dB(A)
Energy class E
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
EA-GA-363BE7-A27 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · High speed (Δ)
43.430 kW Sensible capacity 31.481 kW Fluid flow 13.64 m³/h Pressure drop 118.5 kPa above the recommended pressure drop
Cooling capacity · Low speed (Y)
37.235 kW Sensible capacity 26.912 kW Fluid flow 11.70 m³/h Pressure drop 90.1 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

High speed (Δ)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated ≈ 11.88 ≈ 10.85 ≈ 10.89 ≈ 16.05
8 not rated not rated not rated not rated ≈ 27.23 ≈ 29.36 ≈ 31.67 ≈ 34.27
10 not rated not rated not rated not rated 41.44 43.43 45.95 49.85
12 not rated not rated not rated not rated not rated 56.27 59.86 64.68

Low speed (Y)

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 11.03 ≈ 9.93 ≈ 9.93 ≈ 9.91
8 not rated not rated not rated not rated ≈ 17.78 ≈ 24.70 ≈ 26.98 ≈ 29.58
10 not rated not rated not rated not rated 34.90 37.24 39.53 42.95
12 not rated not rated not rated not rated not rated 48.33 51.45 55.63

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 43.430 13.64 118.5
Low speed (Y) 37.235 11.70 90.1

Dimensions

Dimension drawing of EA-GA-363BE7-A27 C
Dimension drawing
Dimensions as drawn
A 3257 mm
B 1000 mm
C 1010 mm
F 710 mm
E1 968 mm
E2 950 mm
E 2885 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 3257 mm
Width 1000 mm
Height 1010 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.