EA-HL-G-150AE10-A10 C
9.16 kW
Defrost: None
Product code: EA-HL-G-150AE7-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 7,534 m³/h |
|---|---|
| Air throw | 20 m |
| External surface | 47.7 m² |
| Inner volume | 17.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 98 kg |
| Quantity | 1 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 690 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.3 dB(A) |
| Energy class | E |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| EA-HL-G-150AE7-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 4.80 | 4.22 | 4.20 | ≈ 4.21 |
| 8 | not rated | not rated | not rated | not rated | 7.66 | 7.29 | ≈ 7.24 | ≈ 9.08 |
| 10 | not rated | not rated | not rated | not rated | 10.56 | 10.40 | ≈ 12.95 | ≈ 15.48 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 13.55 | ≈ 18.24 | 20.75 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 4.42 | 3.92 | 3.82 | 3.81 |
| 8 | not rated | not rated | not rated | not rated | 6.99 | 6.69 | 6.61 | 6.86 |
| 10 | not rated | not rated | not rated | not rated | 9.58 | 9.47 | ≈ 9.58 | ≈ 13.31 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 12.25 | ≈ 15.58 | ≈ 17.95 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 10.395 | 3.26 | 24.2 |
| Low speed (Y) | 9.472 | 2.97 | 20.5 |
| A | 1387 mm |
|---|---|
| B | 640 mm |
| C | 875 mm |
| F | 560 mm |
| E | 1035 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1387 mm |
|---|---|
| Width | 640 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.