EA-HL-G-350AC7-A10 C
16.42 kW
Defrost: None
Product code: EA-HL-G-250AC10-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 16,255 m³/h |
|---|---|
| Air throw | 23 m |
| External surface | 46.5 m² |
| Inner volume | 23.3 dm³ |
| Fin spacing | 10.0 mm |
| Fin material | Aluminium |
| Net weight | 137 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 1,380 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 84.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EA-HL-G-250AC10-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.51 | 4.86 | ≈ 4.89 | ≈ 4.91 |
| 8 | not rated | not rated | not rated | not rated | 8.88 | ≈ 8.40 | ≈ 11.89 | ≈ 13.86 |
| 10 | not rated | not rated | not rated | not rated | ≈ 12.31 | 16.49 | 18.53 | 20.85 |
| 12 | not rated | not rated | not rated | not rated | not rated | 22.21 | 24.60 | 27.31 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 5.17 | 4.54 | 4.53 | ≈ 4.54 |
| 8 | not rated | not rated | not rated | not rated | 8.27 | 7.86 | ≈ 7.86 | ≈ 12.27 |
| 10 | not rated | not rated | not rated | not rated | 11.41 | 11.23 | ≈ 16.43 | 18.61 |
| 12 | not rated | not rated | not rated | not rated | not rated | 19.57 | 21.89 | 24.38 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 16.486 | 5.18 | 61.0 |
| Low speed (Y) | 11.227 | 3.53 | 30.9 |
| A | 2387 mm |
|---|---|
| B | 590 mm |
| C | 875 mm |
| F | 510 mm |
| E1 | 1018 mm |
| E | 2035 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2387 mm |
|---|---|
| Width | 590 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.