EA-HL-G-350AC10-A10 C
26.33 kW
Defrost: None
Product code: EA-HL-G-350AE4-A10 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 21,530 m³/h |
|---|---|
| Air throw | 22 m |
| External surface | 228.3 m² |
| Inner volume | 50.7 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 246 kg |
| Quantity | 3 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 2,070 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 62.0 dB(A) |
|---|---|
| Sound power | 85.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| EA-HL-G-350AE4-A10 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 11.67 | 11.37 | 11.43 | ≈ 11.46 |
| 8 | not rated | not rated | not rated | not rated | 19.25 | 18.05 | ≈ 18.13 | ≈ 34.09 |
| 10 | not rated | not rated | not rated | not rated | 27.22 | 26.24 | ≈ 47.72 | ≈ 55.57 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 57.31 | 65.86 | 74.27 |
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 10.97 | 10.50 | 10.55 | ≈ 10.56 |
| 8 | not rated | not rated | not rated | not rated | 17.93 | 16.74 | ≈ 16.56 | ≈ 27.29 |
| 10 | not rated | not rated | not rated | not rated | 25.17 | 24.39 | ≈ 39.40 | ≈ 47.31 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 32.27 | ≈ 55.69 | 63.40 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 26.240 | 8.24 | 16.2 |
| Low speed (Y) | 24.394 | 7.66 | 14.2 |
| A | 3387 mm |
|---|---|
| B | 640 mm |
| C | 875 mm |
| F | 560 mm |
| E1 | 1018 mm |
| E2 | 1000 mm |
| E | 3035 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 3387 mm |
|---|---|
| Width | 640 mm |
| Height | 875 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.