EB-G-230AB6-A01 C
2.35 kW
Defrost: None
Product code: EB-G-130BE7-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 1,282 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 9.3 m² |
| Inner volume | 2.6 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 22 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.2 dB(A) |
| Energy class | D |
| Inlet | 1/2" |
|---|---|
| Outlet | 1/2" |
| EB-G-130BE7-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 1.14 | 1.04 | 1.03 | 1.01 |
| 8 | not rated | not rated | not rated | not rated | 1.74 | 1.71 | 1.70 | 1.88 |
| 10 | not rated | not rated | not rated | not rated | 2.34 | 2.35 | ≈ 2.56 | ≈ 3.01 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 2.98 | ≈ 3.50 | 3.93 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 2.351 | 0.74 | 78.8 |
| A | 917 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E | 560 mm |
| D IN | 1/2" |
| D OUT | 1/2" |
| Length | 917 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.