EB-G-430AC6-A01 C
5.19 kW
Defrost: None
Product code: EB-G-140AE6-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 3,181 m³/h |
|---|---|
| Air throw | 11 m |
| External surface | 20.8 m² |
| Inner volume | 5.4 dm³ |
| Fin spacing | 6.0 mm |
| Fin material | Aluminium |
| Net weight | 39 kg |
| Quantity | 1 |
|---|---|
| Diameter | 400 mm |
| Speed | 1,430 rpm |
| Power | 160 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | E |
| Inlet | 3/4" |
|---|---|
| Outlet | 3/4" |
| EB-G-140AE6-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 2.48 | 2.24 | 2.19 | ≈ 2.13 |
| 8 | not rated | not rated | not rated | not rated | 3.87 | 3.74 | ≈ 3.69 | ≈ 4.81 |
| 10 | not rated | not rated | not rated | not rated | 5.25 | 5.23 | ≈ 6.40 | 7.25 |
| 12 | not rated | not rated | not rated | not rated | not rated | 7.55 | 8.51 | 9.46 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 5.229 | 1.64 | 85.7 |
| A | 1077 mm |
|---|---|
| B | 650 mm |
| C | 617 mm |
| F | 445 mm |
| E | 685 mm |
| D IN | 3/4" |
| D OUT | 3/4" |
| Length | 1077 mm |
|---|---|
| Width | 650 mm |
| Height | 617 mm |
Our engineers answer with a selection for your conditions.