EB-G-225BC6-A05 C
2.37 kW
Defrost: None
Product code: EB-G-225AC4-A05 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 1,552 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 13.7 m² |
| Inner volume | 2.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 24 kg |
| Quantity | 2 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 190 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 61.5 dB(A) |
| Energy class | E |
| Inlet | 3/4" |
|---|---|
| Outlet | 3/4" |
| EB-G-225AC4-A05 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 1.10 | 0.98 | 0.96 | ≈ 0.95 |
| 8 | not rated | not rated | not rated | not rated | 1.75 | 1.68 | ≈ 1.65 | ≈ 2.24 |
| 10 | not rated | not rated | not rated | not rated | 2.39 | 2.37 | ≈ 3.05 | ≈ 3.51 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 3.59 | ≈ 4.13 | 4.63 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 2.370 | 0.74 | 54.7 |
| A | 1257 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 438 mm |
| E | 875 mm |
| D IN | 3/4" |
| D OUT | 3/4" |
| Length | 1257 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |