EB-G-430AB4-A01 C
4.60 kW
Defrost: None
Product code: EB-G-230BE4-A05 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 2,069 m³/h |
|---|---|
| Air throw | 5 m |
| External surface | 29.5 m² |
| Inner volume | 5.3 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 35 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | E |
| Inlet | 3/4" |
|---|---|
| Outlet | 3/4" |
| EB-G-230BE4-A05 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 2.20 | 1.99 | 1.95 | ≈ 1.89 |
| 8 | not rated | not rated | not rated | not rated | 3.41 | 3.31 | ≈ 3.26 | ≈ 4.28 |
| 10 | not rated | not rated | not rated | not rated | 4.61 | 4.60 | ≈ 5.68 | 6.45 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 5.92 | ≈ 7.54 | 8.38 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 4.600 | 1.44 | 61.9 |
| A | 1417 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 518 mm |
| E | 1035 mm |
| D IN | 3/4" |
| D OUT | 3/4" |
| Length | 1417 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.