EB-G-130AE4-A01 C
2.40 kW
Defrost: None
Product code: EB-G-325AB7-A05 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 2,587 m³/h |
|---|---|
| Air throw | 6 m |
| External surface | 9.8 m² |
| Inner volume | 3.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 30 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 285 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.5 dB(A) |
| Energy class | E |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| EB-G-325AB7-A05 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 1.12 | 1.00 | 0.98 | ≈ 0.96 |
| 8 | not rated | not rated | not rated | not rated | 1.77 | 1.71 | ≈ 1.70 | ≈ 2.44 |
| 10 | not rated | not rated | not rated | not rated | 2.42 | 2.41 | ≈ 3.23 | 3.67 |
| 12 | not rated | not rated | not rated | not rated | not rated | 3.80 | 4.29 | 4.79 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 2.406 | 0.76 | 63.4 |
| A | 1677 mm |
|---|---|
| B | 520 mm |
| C | 363 mm |
| F | 345 mm |
| E1 | 438 mm |
| E2 | 420 mm |
| E | 1295 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 1677 mm |
|---|---|
| Width | 520 mm |
| Height | 363 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.