EB-G-430AE4-A01 C
7.65 kW
Defrost: None
Product code: EB-G-430BE7-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 5,132 m³/h |
|---|---|
| Air throw | 7 m |
| External surface | 37.2 m² |
| Inner volume | 11.0 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 56 kg |
| Quantity | 4 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 248 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 48.0 dB(A) |
|---|---|
| Sound power | 70.2 dB(A) |
| Energy class | E |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| EB-G-430BE7-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 3.62 | 3.23 | 3.15 | 3.09 |
| 8 | not rated | not rated | not rated | not rated | 5.69 | 5.48 | 5.37 | ≈ 5.64 |
| 10 | not rated | not rated | not rated | not rated | 7.78 | 7.72 | ≈ 7.83 | ≈ 11.91 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 9.96 | ≈ 13.85 | 15.60 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 7.716 | 2.42 | 38.8 |
| A | 2417 mm |
|---|---|
| B | 520 mm |
| C | 426 mm |
| F | 345 mm |
| E1 | 543 mm |
| E2 | 525 mm |
| E | 2135 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 2417 mm |
|---|---|
| Width | 520 mm |
| Height | 426 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.