EB-G-340AE6-A01 C
13.03 kW
Defrost: None
Product code: EB-G-435AE4-A01 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 9,378 m³/h |
|---|---|
| Air throw | 12 m |
| External surface | 94.4 m² |
| Inner volume | 17.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 86 kg |
| Quantity | 4 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 660 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 54.0 dB(A) |
|---|---|
| Sound power | 76.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| EB-G-435AE4-A01 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 6.10 | 5.73 | 5.76 | 5.74 |
| 8 | not rated | not rated | not rated | not rated | 9.82 | 9.25 | 9.07 | ≈ 9.23 |
| 10 | not rated | not rated | not rated | not rated | 13.64 | 13.31 | ≈ 13.25 | ≈ 23.06 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 17.45 | ≈ 27.05 | 30.99 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 13.312 | 4.18 | 26.0 |
| A | 2817 mm |
|---|---|
| B | 520 mm |
| C | 553 mm |
| F | 345 mm |
| E1 | 618 mm |
| E2 | 600 mm |
| E | 2435 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 2817 mm |
|---|---|
| Width | 520 mm |
| Height | 553 mm |