ED-G-330AC4-A21 C
8.17 kW
Defrost: None
Product code: ED-G-145AC4-A23 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 4,665 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 32.5 m² |
| Inner volume | 9.5 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 63 kg |
| Quantity | 1 |
|---|---|
| Diameter | 450 mm |
| Speed | 1,300 rpm |
| Power | 350 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 80.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| ED-G-145AC4-A23 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 2.73 | 2.43 | ≈ 2.45 | ≈ 2.46 |
| 8 | not rated | not rated | not rated | not rated | 4.42 | ≈ 4.18 | ≈ 5.56 | ≈ 6.56 |
| 10 | not rated | not rated | not rated | not rated | ≈ 6.15 | 7.98 | 8.89 | 9.97 |
| 12 | not rated | not rated | not rated | not rated | not rated | 10.78 | 11.86 | 13.14 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 7.983 | 2.51 | 77.7 |
| A | 1208 mm |
|---|---|
| B | 1210 mm |
| C | 365 mm |
| F | 1135 mm |
| G | 441 mm |
| E1 | 835 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1208 mm |
|---|---|
| Width | 1210 mm |
| Height | 441 mm |
Our engineers answer with a selection for your conditions.