ED-G-445AC4-A23 C
28.92 kW
Defrost: None
Product code: ED-G-250AG7-A21 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 13,215 m³/h |
|---|---|
| Air throw | 13 m |
| External surface | 114.5 m² |
| Inner volume | 40.2 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 163 kg |
| Quantity | 2 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,300 rpm |
| Power | 1,360 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 81.1 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| ED-G-250AG7-A21 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 9.95 | 8.75 | ≈ 8.74 | ≈ 8.72 |
| 8 | not rated | not rated | not rated | not rated | 15.88 | ≈ 15.10 | ≈ 20.12 | ≈ 24.48 |
| 10 | not rated | not rated | not rated | not rated | ≈ 21.90 | 28.83 | 32.47 | 36.26 |
| 12 | not rated | not rated | not rated | not rated | not rated | 38.61 | 42.64 | 47.10 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 28.834 | 9.05 | 57.0 |
| A | 2428 mm |
|---|---|
| B | 1350 mm |
| C | 405 mm |
| F | 1135 mm |
| G | 506 mm |
| E1 | 2035 mm |
| E2 | 1018 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2428 mm |
|---|---|
| Width | 1350 mm |
| Height | 506 mm |
Our engineers answer with a selection for your conditions.