Skip to Content

Brine cooler ED-G-530AC4-A21 C

Brine cooler ED-G-530AC4-A21 C
Illustrative photo

Producer: Karyer · Line: ED-G (General)

Product code: ED-G-530AC4-A21 C

Cooling capacity i
13.65 kW
Air flow
6,593 m³/h
Fin spacing
4.2 mm
Air throw
9 m
Fans
5 × ⌀300 mm

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Data

Coil
Air flow 6,593 m³/h
Air throw 9 m
External surface 63.0 m²
Inner volume 13.8 dm³
Fin spacing 4.2 mm
Fin materialAluminium
Net weight 114 kg
Fans
Quantity 5
Diameter 300 mm
Speed 1,380 rpm
Power 310 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 49.0 dB(A)
Sound power 71.1 dB(A)
Energy class D
Connections
Inlet 1 1/2"
Outlet 1 1/2"
Defrost
ED-G-530AC4-A21 C None

Performance

Fluid -10 → -7 °C

ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.

ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)

Cooling capacity · Single phase
13.647 kW Sensible capacity 9.846 kW Fluid flow 4.29 m³/h Pressure drop 93.6 kPa above the recommended pressure drop

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K

ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

≈ 1.23 estimate — vendor data irregular here

Single phase

Cooling capacity [kW]: Air inlet × ΔT (air − fluid inlet), fluid range 3 K
ΔT [K] \ air [°C] -25-20-15-10-50510
6 not rated not rated not rated not rated 3.53 ≈ 3.21 ≈ 3.23 ≈ 3.24
8 not rated not rated not rated not rated ≈ 5.80 ≈ 8.49 ≈ 9.68 ≈ 11.22
10 not rated not rated not rated not rated ≈ 12.28 13.65 14.94 16.56
12 not rated not rated not rated not rated not rated 17.94 19.59 21.57

Nominal rating

Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %

Fan connection Cooling capacity [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 13.647 4.29 93.6

Dimensions

Dimension drawing of ED-G-530AC4-A21 C
Dimension drawing
Dimensions as drawn
A 2908 mm
B 1030 mm
C 245 mm
F 985 mm
G 305 mm
E1 2535 mm
E2 518 mm
E3 500 mm
D IN 1 1/2"
D OUT 1 1/2"
Overall [mm]
Length 2908 mm
Width 1030 mm
Height 305 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.