EG-G-125BE4-A23 C
1.47 kW
Defrost: None
Product code: EG-G-130BC7-A21 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 1,293 m³/h |
|---|---|
| Air throw | 8 m |
| External surface | 5.0 m² |
| Inner volume | 1.9 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 19 kg |
| Quantity | 1 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 62 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 64.1 dB(A) |
| Energy class | E |
| Inlet | 1" |
|---|---|
| Outlet | 1" |
| EG-G-130BC7-A21 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 0.70 | 0.63 | 0.62 | 0.60 |
| 8 | not rated | not rated | not rated | not rated | 1.09 | 1.05 | 1.05 | 1.10 |
| 10 | not rated | not rated | not rated | not rated | 1.48 | 1.47 | ≈ 1.51 | ≈ 1.91 |
| 12 | not rated | not rated | not rated | not rated | not rated | ≈ 1.89 | ≈ 2.23 | 2.55 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 1.473 | 0.46 | 54.4 |
| A | 826 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E | 515 mm |
| D IN | 1" |
| D OUT | 1" |
| Length | 826 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.