EG-G-135BC4-A21 C
2.39 kW
Defrost: None
Product code: EG-G-230BB4-A25 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 2,310 m³/h |
|---|---|
| Air throw | 9 m |
| External surface | 11.8 m² |
| Inner volume | 3.0 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 29 kg |
| Quantity | 2 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,300 rpm |
| Power | 240 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 43.0 dB(A) |
|---|---|
| Sound power | 65.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/4" |
|---|---|
| Outlet | 1 1/4" |
| EG-G-230BB4-A25 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 1.09 | 0.96 | 0.96 | ≈ 0.96 |
| 8 | not rated | not rated | not rated | not rated | 1.74 | 1.66 | ≈ 1.65 | ≈ 2.35 |
| 10 | not rated | not rated | not rated | not rated | 2.41 | 2.37 | ≈ 3.25 | ≈ 3.74 |
| 12 | not rated | not rated | not rated | not rated | not rated | 3.89 | 4.43 | 4.97 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 2.369 | 0.74 | 49.4 |
| A | 1306 mm |
|---|---|
| B | 685 mm |
| C | 370 mm |
| F | 630 mm |
| E1 | 498 mm |
| E | 995 mm |
| D IN | 1 1/4" |
| D OUT | 1 1/4" |
| Length | 1306 mm |
|---|---|
| Width | 685 mm |
| Height | 370 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.