EG-G-430BC4-A21 C
4.78 kW
Defrost: None
Product code: EG-G-235CE7-A21 C
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Air flow | 4,047 m³/h |
|---|---|
| Air throw | 14 m |
| External surface | 19.5 m² |
| Inner volume | 6.4 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 44 kg |
| Quantity | 2 |
|---|---|
| Diameter | 350 mm |
| Speed | 1,340 rpm |
| Power | 330 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 73.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| EG-G-235CE7-A21 C | None |
|---|
ΔT (air inlet − fluid inlet) must be within 6–12 K (fluid outlet = inlet + 3 K); air inlet -25…10 °C. Points below the fluid's freezing point are not rated.
ETHYLENE GLYCOL 30% -10 → -7 °C, air inlet 0 °C (ΔT 10 K)
ETHYLENE GLYCOL 30%; rows: ΔT = air inlet − fluid inlet [K], outlet = inlet + 3 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| ΔT [K] \ air [°C] | -25 | -20 | -15 | -10 | -5 | 0 | 5 | 10 |
|---|---|---|---|---|---|---|---|---|
| 6 | not rated | not rated | not rated | not rated | 2.21 | 1.95 | 1.94 | 1.94 |
| 8 | not rated | not rated | not rated | not rated | 3.52 | 3.36 | 3.31 | ≈ 3.40 |
| 10 | not rated | not rated | not rated | not rated | 4.85 | 4.79 | ≈ 4.81 | ≈ 6.86 |
| 12 | not rated | not rated | not rated | not rated | not rated | 6.23 | ≈ 6.38 | ≈ 9.58 |
Nominal conditions: ethylene glycol 30 % −10 → −7 °C, air inlet 0 °C, relative humidity 85 %
| Fan connection | Cooling capacity [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 4.786 | 1.50 | 20.0 |
| A | 1746 mm |
|---|---|
| B | 680 mm |
| C | 355 mm |
| F | 650 mm |
| E1 | 718 mm |
| E | 1435 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 1746 mm |
|---|---|
| Width | 680 mm |
| Height | 355 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.