- Catalogue
- CO₂ DX evaporators
- EG-DC (Angled Ceiling Type)
- EG-DC-325BE4-A23 C
CO2 evaporator EG-DC-325BE4-A23 C
Defrost: None
Product code: EG-DC-325BE4-A23 C
- Fin spacing
- 4.2 mm
- Fans
- 3 × ⌀250 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Data
| External surface | 26.6 m² |
|---|---|
| Inner volume | 4.1 dm³ |
| Fin spacing | 4.2 mm |
| Fin material | Aluminium |
| Net weight | 42 kg |
| Quantity | 3 |
|---|---|
| Diameter | 250 mm |
| Speed | 1,300 rpm |
| Power | 195 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 42.0 dB(A) |
|---|---|
| Sound power | 63.4 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø9,52 |
| EG-DC-325BE4-A23 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 3.989 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.78 | 1.79 | 1.81 | 1.84 | 1.87 | 1.89 | 1.91 | 1.97 | 2.10 | 2.30 | 2.28 | 2.27 | 2.26 | 2.24 |
| 5 | 2.22 | 2.23 | 2.27 | 2.32 | 2.36 | 2.39 | 2.41 | 2.47 | 2.63 | 2.87 | 2.83 | 2.82 | 2.79 | 2.75 |
| 6 | 2.65 | 2.68 | 2.73 | 2.80 | 2.85 | 2.89 | 2.91 | 2.97 | 3.16 | 3.45 | 3.40 | 3.37 | 3.34 | 3.27 |
| 7 | 3.07 | 3.12 | 3.19 | 3.27 | 3.34 | 3.39 | 3.42 | 3.48 | 3.70 | 4.03 | 3.97 | 3.94 | 3.89 | 3.80 |
| 8 | 3.48 | 3.54 | 3.63 | 3.74 | 3.82 | 3.88 | 3.92 | 3.99 | 4.24 | 4.62 | 4.54 | 4.50 | 4.44 | 4.34 |
| 9 | 3.87 | 3.95 | 4.07 | 4.20 | 4.30 | 4.37 | 4.42 | 4.50 | 4.79 | 5.21 | 5.12 | 5.08 | 5.00 | 4.88 |
| 10 | 4.25 | 4.35 | 4.50 | 4.65 | 4.77 | 4.86 | 4.92 | 5.01 | 5.33 | 5.80 | 5.70 | 5.65 | 5.57 | 5.42 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.699 |
| SC2 | 0 | 8 | 3.989 |
| SC3 | -18 | 7 | 3.300 |
| SC4 | -25 | 6 | 2.732 |
| SC5 | -34 | 6 | 2.660 |
Dimensions
| A | 2146 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 618 mm |
| E2 | 600 mm |
| E | 1835 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø9,52 |
| Length | 2146 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |