CO2 evaporator EG-DC-330AB7-A21 C
Defrost: None
Product code: EG-DC-330AB7-A21 C
- Fin spacing
- 7.0 mm
- Fans
- 3 × ⌀300 mm
Nominal conditions: refrigerant R404A, evaporation (dew point) −8 °C, inlet air 0 °C, humidity 85 %
Data
| External surface | 11.0 m² |
|---|---|
| Inner volume | 2.5 dm³ |
| Fin spacing | 7.0 mm |
| Fin material | Aluminium |
| Net weight | 48 kg |
| Quantity | 3 |
|---|---|
| Diameter | 300 mm |
| Speed | 1,380 rpm |
| Power | 186 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 47.0 dB(A) |
|---|---|
| Sound power | 69.3 dB(A) |
| Energy class | D |
| Inlet | Ø9,52 |
|---|---|
| Outlet | Ø12,7 |
| EG-DC-330AB7-A21 C | None |
|---|
Performance
TD (air − evaporating) must be within 4–10 K; air inlet −40…+20 °C.
R744, dew point -8 °C, air inlet 0 °C (TD 8 K)
- Single phase
- 3.718 kW
Capacity matrix [kW]
R744, Dew point; rows: TD = air inlet − evaporating temperature, columns: air inlet temperature. The highlighted cell is the nominal point (SC2). "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
Single phase
| TD [K] \ air [°C] | -35 | -30 | -25 | -20 | -15 | -10 | -5 | 0 | 2 | 5 | 10 | 12 | 15 | 20 |
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| 4 | 1.57 | 1.56 | 1.58 | 1.60 | 1.63 | 1.65 | 1.67 | 1.73 | 1.85 | 2.03 | 2.03 | 2.03 | 2.04 | 2.06 |
| 5 | 2.01 | 2.00 | 2.02 | 2.06 | 2.10 | 2.13 | 2.16 | 2.21 | 2.37 | 2.60 | 2.59 | 2.58 | 2.58 | 2.59 |
| 6 | 2.44 | 2.44 | 2.47 | 2.52 | 2.57 | 2.61 | 2.65 | 2.71 | 2.89 | 3.17 | 3.15 | 3.14 | 3.14 | 3.13 |
| 7 | 2.88 | 2.88 | 2.93 | 2.99 | 3.05 | 3.10 | 3.14 | 3.21 | 3.43 | 3.75 | 3.72 | 3.71 | 3.69 | 3.68 |
| 8 | 3.30 | 3.32 | 3.38 | 3.46 | 3.53 | 3.59 | 3.64 | 3.72 | 3.97 | 4.34 | 4.30 | 4.28 | 4.26 | 4.23 |
| 9 | 3.72 | 3.75 | 3.83 | 3.92 | 4.01 | 4.08 | 4.14 | 4.23 | 4.51 | 4.93 | 4.88 | 4.86 | 4.83 | 4.79 |
| 10 | 4.14 | 4.18 | 4.27 | 4.39 | 4.49 | 4.58 | 4.65 | 4.74 | 5.05 | 5.52 | 5.47 | 5.45 | 5.41 | 5.35 |
Standard ratings (EN 328 / Eurovent)
| Standard condition | Air inlet [°C] | TD [K] | Single phase [kW] |
|---|---|---|---|
| SC1 | 10 | 10 | 5.470 |
| SC2 | 0 | 8 | 3.718 |
| SC3 | -18 | 7 | 3.017 |
| SC4 | -25 | 6 | 2.472 |
| SC5 | -34 | 6 | 2.443 |
Dimensions
| A | 2746 mm |
|---|---|
| B | 685 mm |
| C | 245 mm |
| F | 630 mm |
| E1 | 818 mm |
| E2 | 800 mm |
| E | 2435 mm |
| D IN | 1 x Ø9,52 |
| D OUT | 1 x Ø12,7 |
| Length | 2746 mm |
|---|---|
| Width | 685 mm |
| Height | 245 mm |