Skip to Content

Condenser KA/KB-150BC5-B01I C

Condenser KA/KB-150BC5-B01I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-150BC5-B01I C

Heat rejection i
24.74 kW
Air flow
6,958 m³/h
Fin spacing
2.5 mm
Fans
1 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 6,958 m³/h
External surface 66.3 m²
Inner volume 8.5 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 102 kg
Fans
Quantity 1
Diameter 500 mm
Speed 1,390 rpm
Power 720 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 40.0 dB(A)
Sound power 71.4 dB(A)
Energy class D
Connections
Inlet Ø19
Outlet Ø16
Defrost
KA/KB-150BC5-B01I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
25.040 kW Refrigerant flow 586 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 25.04 25.11 25.23 25.42 25.73 26.22

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 25.040

Dimensions

Dimension drawing of KA/KB-150BC5-B01I C
Dimension drawing
Dimensions as drawn
A 1100 mm
B 1200 mm
C 920 mm
F 1050 mm
G 450 mm
E 900 mm
H 800 mm
I 870 mm
D IN Ø19
D OUT Ø16
Overall [mm]
Length 1100 mm
Width 920 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.