Skip to Content

Condenser KA/KB-163BC1-B01 C

Condenser KA/KB-163BC1-B01 C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-163BC1-B01 C

Heat rejection i
34.47 kW
Air flow
8,398 m³/h
Fin spacing
2.1 mm
Fans
1 × ⌀630 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 8,398 m³/h
External surface 93.1 m²
Inner volume 9.9 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 129 kg
Fans
Quantity 1
Diameter 630 mm
Speed 860 rpm
Power 600 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 43.0 dB(A)
Sound power 74.1 dB(A)
Energy class D
Connections
Inlet Ø22
Outlet Ø19
Defrost
KA/KB-163BC1-B01 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
34.873 kW Refrigerant flow 817 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 34.87 34.89 34.95 35.08 35.31 35.71

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 34.873

Dimensions

Dimension drawing of KA/KB-163BC1-B01 C
Dimension drawing
Dimensions as drawn
A 1200 mm
B 1200 mm
C 1230 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 1180 mm
D IN Ø22
D OUT Ø19
Overall [mm]
Length 1200 mm
Width 1230 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.