Skip to Content

Condenser KA/KB-2x291GC5-B04I C

Condenser KA/KB-2x291GC5-B04I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-2x291GC5-B04I C

Heat rejection i
325.47 kW
Air flow
109,584 m³/h
Fin spacing
2.5 mm
Fans
4 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 109,584 m³/h
External surface 605.2 m²
Inner volume 79.1 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 732 kg
Fans
Quantity 4
Diameter 910 mm
Speed 840 rpm
Power 11,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 64.0 dB(A)
Sound power 95.9 dB(A)
Energy class E
Connections
Inlet Ø42
Outlet Ø42
Defrost
KA/KB-2x291GC5-B04I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
329.531 kW Refrigerant flow 7,717 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 329.53 331.22 333.78 337.56 343.15 351.85

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 329.531

Dimensions

Dimension drawing of KA/KB-2x291GC5-B04I C
Dimension drawing
Dimensions as drawn
A 3800 mm
B 1520 mm
C 2310 mm
F 1050 mm
G 450 mm
E 3600 mm
H 1750 mm
I 2260 mm
D IN Ø42
D OUT Ø42
Overall [mm]
Length 3800 mm
Width 2310 mm
Height 1520 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.