KA/KB-t-363HA5-B08 C
135.66 kW
Defrost: None
Product code: KA/KB-2x350BB1-B10 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 43,196 m³/h |
|---|---|
| External surface | 353.0 m² |
| Inner volume | 42.9 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 384 kg |
| Quantity | 6 |
|---|---|
| Diameter | 500 mm |
| Speed | 1,360 rpm |
| Power | 4,140 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | Ø42 |
|---|---|
| Outlet | Ø35 |
| KA/KB-2x350BB1-B10 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 137.39 | 137.96 | 138.90 | 140.35 | 142.55 | 146.09 |
| Low speed (Y) | 117.03 | 117.38 | 118.04 | 119.12 | 120.83 | 123.62 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 137.391 |
| Low speed (Y) | 117.032 |
| A | 2700 mm |
|---|---|
| B | 1200 mm |
| C | 1720 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2500 mm |
| H | 800 mm |
| I | 1670 mm |
| D IN | Ø42 |
| D OUT | Ø35 |
| Length | 2700 mm |
|---|---|
| Width | 1720 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.