Skip to Content

Condenser KA/KB-2x550CB5-B04 C

Condenser KA/KB-2x550CB5-B04 C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-2x550CB5-B04 C

Heat rejection i
156.96 kW
Air flow
50,515 m³/h
Fin spacing
2.5 mm
Fans
10 × ⌀500 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 50,515 m³/h
External surface 376.5 m²
Inner volume 49.7 dm³
Fin spacing 2.5 mm
Fin materialAluminium
Net weight 557 kg
Fans
Quantity 10
Diameter 500 mm
Speed 910 rpm
Power 3,000 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 47.0 dB(A)
Sound power 79.1 dB(A)
Energy class D
Connections
Inlet Ø42
Outlet Ø42
Defrost
KA/KB-2x550CB5-B04 C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
158.878 kW Refrigerant flow 3,721 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 158.88 159.43 160.36 161.80 164.01 167.48

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 158.878

Dimensions

Dimension drawing of KA/KB-2x550CB5-B04 C
Dimension drawing
Dimensions as drawn
A 4300 mm
B 1200 mm
C 1710 mm
F 1050 mm
G 450 mm
E 4100 mm
H 800 mm
I 1660 mm
D IN Ø42
D OUT Ø42
Overall [mm]
Length 4300 mm
Width 1800 mm
Height 1200 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.