Skip to Content

Condenser KA/KB-2x591BB1-B04I C

Condenser KA/KB-2x591BB1-B04I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-2x591BB1-B04I C

Heat rejection i
666.98 kW
Air flow
260,548 m³/h
Fin spacing
2.1 mm
Fans
10 × ⌀910 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 260,548 m³/h
External surface 1,441.4 m²
Inner volume 171.4 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 1,576 kg
Fans
Quantity 10
Diameter 910 mm
Speed 840 rpm
Power 28,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 68.0 dB(A)
Sound power 100.2 dB(A)
Energy class E
Connections
Inlet Ø66,7
Outlet Ø54
Defrost
KA/KB-2x591BB1-B04I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
675.884 kW Refrigerant flow 15,828 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 675.88 680.66 688.16 699.44 716.39 743.62

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 675.884

Dimensions

Dimension drawing of KA/KB-2x591BB1-B04I C
Dimension drawing
Dimensions as drawn
A 7300 mm
B 1520 mm
C 2360 mm
F 1050 mm
G 450 mm
E 7100 mm
H 1400 mm
I 2310 mm
D IN Ø66,7
D OUT Ø54
Overall [mm]
Length 7300 mm
Width 2360 mm
Height 1520 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.