Skip to Content

Condenser KA/KB-2x680CB1-B01I C

Condenser KA/KB-2x680CB1-B01I C
Illustrative photo

Producer: Karyer · Line: KA/KB (General)

Product code: KA/KB-2x680CB1-B01I C

Heat rejection i
522.46 kW
Air flow
199,415 m³/h
Fin spacing
2.1 mm
Fans
12 × ⌀800 mm

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Data

Coil
Air flow 199,415 m³/h
External surface 964.5 m²
Inner volume 108.4 dm³
Fin spacing 2.1 mm
Fin materialAluminium
Net weight 1,473 kg
Fans
Quantity 12
Diameter 800 mm
Speed 880 rpm
Power 23,484 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 61.0 dB(A)
Sound power 93.2 dB(A)
Energy class E
Connections
Inlet Ø54
Outlet Ø54
Defrost
KA/KB-2x680CB1-B01I C None

Performance

Condensing 40 °C

ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.

R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)

Heat rejection · Single phase
529.143 kW Refrigerant flow 12,391 kg/h

Heat rejection at ΔT 15 K [kW]

R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Heat rejection at ΔT 15 K [kW]
Fan connection \ air [°C] 253035404550
Single phase 529.14 532.89 538.28 545.99 557.19 574.51

Nominal rating

Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %

Fan connection Heat rejection [kW]
Single phase 529.143

Dimensions

Dimension drawing of KA/KB-2x680CB1-B01I C
Dimension drawing
Dimensions as drawn
A 6600 mm
B 1350 mm
C 2310 mm
F 1050 mm
G 450 mm
E 6400 mm
H 1050 mm
I 2260 mm
D IN Ø54
D OUT Ø54
Overall [mm]
Length 6600 mm
Width 2310 mm
Height 1350 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.