KA/KB-2x691BC1-B04 C
957.62 kW
Defrost: None
Product code: KA/KB-2x680FD1-B01I C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 213,802 m³/h |
|---|---|
| External surface | 3,603.6 m² |
| Inner volume | 399.9 dm³ |
| Fin spacing | 2.1 mm |
| Fin material | Aluminium |
| Net weight | 2,570 kg |
| Quantity | 12 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 23,484 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.8 dB(A) |
| Energy class | D |
| Inlet | Ø66,7 |
|---|---|
| Outlet | Ø54 |
| KA/KB-2x680FD1-B01I C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| Single phase | 968.16 | 965.01 | 963.42 | 963.93 | 967.26 | 974.78 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| Single phase | 968.157 |
| A | 10800 mm |
|---|---|
| B | 1350 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 10600 mm |
| H | 1750 mm |
| I | 2310 mm |
| D IN | Ø66,7 |
| D OUT | Ø54 |
| Length | 10800 mm |
|---|---|
| Width | 2360 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.