KA/KB-2x680FC1-B01I C
885.58 kW
Defrost: None
Product code: KA/KB-2x780AD5-B01 C
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Air flow | 232,821 m³/h |
|---|---|
| External surface | 2,437.6 m² |
| Inner volume | 324.3 dm³ |
| Fin spacing | 2.5 mm |
| Fin material | Aluminium |
| Net weight | 2,278 kg |
| Quantity | 14 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 25,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 61.0 dB(A) |
|---|---|
| Sound power | 93.3 dB(A) |
| Energy class | D |
| Inlet | Ø66,7 |
|---|---|
| Outlet | Ø54 |
| KA/KB-2x780AD5-B01 C | None |
|---|
ΔT (condensing − air inlet) must be within 8–20 K; air inlet 25…50 °C.
R404A, dew point, air inlet 25 °C, ΔT 15 K (condensing 40 °C); Vendor rating (gas inlet superheat 26 K, no subcooling)
R404A, Vendor rating (gas inlet superheat 26 K, no subcooling); one row per fan connection; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fan connection \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| High speed (Δ) | 899.99 | 902.18 | 906.81 | 914.54 | 926.69 | 946.56 |
| Low speed (Y) | 689.00 | 689.82 | 692.42 | 697.34 | 704.90 | 717.63 |
Nominal conditions (EN 327): air inlet 25 °C, condensing temperature 40 °C (ΔT 15 K), gas inlet superheat 26 K, no subcooling, relative humidity 50 %
| Fan connection | Heat rejection [kW] |
|---|---|
| High speed (Δ) | 899.986 |
| Low speed (Y) | 688.997 |
| A | 8700 mm |
|---|---|
| B | 1350 mm |
| C | 2360 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 8500 mm |
| H | 1200 mm |
| I | 2310 mm |
| D IN | Ø66,7 |
| D OUT | Ø54 |
| Length | 8700 mm |
|---|---|
| Width | 2360 mm |
| Height | 1350 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.